Home / Resources / R-290 (Propane) Reference
Thermodynamic Gas Center

R-290 (Propane) Datasheet

View pressure-temperature formulas, safety classifications, environmental impact coefficients (GWP/ODP), oil compatibility, leak checking, and retrofit instructions.

Formula
C3H8
Safety Class
A3 (Highly Flammable)
Global Warming (GWP)
3
Ozone Impact (ODP)
0

Interactive Saturation pressure calculator

Enter a custom system temperature to dynamically compute the refrigerant's bubble/dew pressure point using the Antoine equation model.

Saturated Temperature:25°C
−40°C0°C20°C40°C60°C
Saturation Vapor Pressure
9.38 Bar
Saturation Vapor Pressure
136.0 PSI

Pressure-Temperature Reference Sheet

Temperature (°C)Pressure (Bar)Pressure (PSI)
-30°C1.67 bar24.2 psi
-15°C2.90 bar42.1 psi
0°C4.71 bar68.3 psi
15°C7.23 bar104.9 psi
30°C10.60 bar153.8 psi
45°C14.95 bar216.8 psi

Compatible Lubricants & Charging

Compatible Oils

Mineral Oil (MO) or POE Oil

Charging Procedures
  • Highly flammable hydrocarbon. Max charge weight limit is strictly capped (typically 150g in India).
  • Charge in liquid or vapor phase in a well-ventilated space with no ignition sources.

Leak Checking & Eco Recovery

Leak Detection Methods
  • HC-compatible combustible gas sniffer
  • Soap bubble solution
Recovery & Recycling
  • Recover using specialized HC-safe machines or vent carefully in open outdoor air where permitted by local code.
Retrofitting & Gas Substitution Advice

Do not retrofit R-290 into systems not designed for hydrocarbons due to explosion risks.